One of the common problems with the Monarch system
1、Q: Why does the main control board always display 888 after power-on?
A: After the power is turned on, the main control board always displays 888 because the program initialization is unsuccessful.
2、Q: Why is the display still not displayed after the external board is connected?
A: It is caused by a mistake in the communication. Check parameters F5-33, F5-33 bit0=1
3、Q: Why does the external signboard only display the floor without the maintenance sign and direction arrow?
A: It is caused by a mistake in the communication.
4、Q: Why does the elevator switch to normal and the elevator does not return to the leveling floor to open the door immediately?
A: The signal in the door area is abnormal.
5、Q: Why does the automatic rescue drive open without opening the floor?
A: Because the door area signal is wrong.
6、Q: Why does the fire door not open after returning to the base?
A: The door open signal is wrong.
The F5-35 monitors whether the door open signal works normally, and 1:C lights up after the door is opened.
7、 Q: Why does the elevator run on every floor without any instructions?
A: The door open signal is wrong.
The F5-35 monitors whether the door open signal works normally, and 1:C lights up after the door is opened.
8、Q: Why is the rectifier bridge of the brake circuit vulnerable to damage?
A: The rectifier bridge is damaged due to the reverse impact when the brake is released. An absorption device can be added to the brake coil: detailed connection and specifications:
9、 Q: Why is the elevator running process seriously jittery?
A:1. Check if there is any problem with the mechanical installation, such as if the guide shoe is too tight;
10、 Q: Why is it good or be bad at leveling, suddenly going up and down?
A: In the case of ensuring that the level sensor is installed correctly: